A chiller is a machine that removes heat from a liquid coolant via a vapor-compression, adsorption refrigeration, or absorption refrigeration cycles. This liquid can then be circulated through a heat exchanger to cool equipment, or another process stream (such as air or process water). As a necessary by-product, refrigeration creates waste heat that must be exhausted to ambience, or for greater efficiency, recovered for heating purposes. Vapor compression chillers may use any of a number of different types of compressors. Most common today are the hermetic scroll, semi-hermetic screw, or centrifugal compressors. The condensing side of the chiller can be either air or water cooled. Even when liquid cooled, the chiller is often cooled by an induced or forced draft cooling tower. Absorption and adsorption chillers require a heat source to function.

Chilled water is used to cool and dehumidify air in mid- to large-size commercial, industrial, and institutional facilities. Water cooled chillers can be evaporatively cooled via a cooling tower, exhausting to air like an air-cooled chiller or cooled via other sources such as river water. Water or liquid-cooled systems can provide efficiency and environmental impact advantages over air-cooled systems.

Use in air conditioning (process cooling)

In air conditioning systems, chilled coolant, usually chilled water mixed with ethylene glycol, from a chiller in an air conditioning or cooling plant is typically distributed to heat exchangers, or coils, in air handlers or other types of terminal devices which cool the air in their respective . The water is then recirculated to the chiller to be recooled. These cooling coils transfer sensible heat and latent heat from the air to the chilled water, thus cooling and usually dehumidifying the air stream. A typical chiller for air conditioning applications is rated between and , and at least two manufacturers (York international and LG) can produce chillers capable of up to cooling. Chilled water temperatures (leaving from the chiller) usually range from , depending upon application requirements. Commonly, chillers receive water at 12°C (entering temperature), and cool it to 7°C (leaving temperature).

When the chillers for air conditioning systems are not operable or they are in need of repair or replacement, emergency chillers may be used to supply chilled water. Rental chillers are mounted on a trailer so that they can be quickly deployed to the site. Large chilled water hoses are used to connect between rental chillers and air conditioning systems.

Chillers can be positive (high) pressure or negative (low) pressure depending on the refrigerant, R22, R134a, R1234ze(E), and R1234yf are positive pressure and R1233zd(E), R1224yd(Z), R514A and R123 are negative pressure. Positive pressure chillers operate at internal pressures higher than ambient pressure, and negative pressure chillers operate under a partial vacuum internally. Negative pressure chillers exhibit higher thermodynamic efficiency, are heavier as they are larger for the same cooling capacity and need continuous purging as they are more susceptible to environmental contamination due to their internal vacuum. Air leaks into these chillers can significantly reduce their performance. They are also more susceptible to corrosion due to the refrigerant such as R123 which is corrosive. Low pressure refrigerants need a higher compression ratio due to their high specific gas volume.

The higher compression ratio is achieved with larger impellers or compressors with 2 or more stages, increasing cost. Also, to keep flow rate adequate with a high specific gas volume, larger heat exchangers are required, increasing weight and related material costs. Due to these reasons, low pressure refrigerants are mostly used in small and medium capacity chillers. Negative pressure refrigerants tend to have a higher latent heat of evaporation which leads to higher efficiency.Mitsubishi Heavy Indusries. Current Status and Future Prospects for Centrifugal Chillers with Low GWP refrigerants

Use in industry In industrial applications, chilled water or other coolant liquid from the chiller is pumped through process or laboratory equipment. Industrial chillers are used for controlled cooling of products, mechanisms and factory machinery in a wide range of industries. They are often used in the plastic industries, injection and blow molding, metalworking cutting oils, welding equipment, die-casting and machine tooling, chemical processing, pharmaceutical formulation, food and beverage processing, paper and cement processing, vacuum systems, X-ray diffraction, power supplies and gas turbine power generation stations (see Turbine inlet air cooling#Vapour compression chiller), analytical equipment, semiconductors, compressed air and gas cooling. They are also used to cool high-heat specialized items such as MRI machines and lasers in hospitals, hotels, and campuses.

Chillers for industrial applications can be centralized, where a single chiller serves multiple cooling needs, or decentralized where each application or machine has its own chiller. Each approach has its advantages. It is also possible to have a combination of both centralized and decentralized chillers, especially if the cooling requirements are the same for some applications or points of use, but not all.

Chilled water is used to cool and dehumidify air in mid- to large-size commercial, industrial, and institutional (CII) facilities. Liquid chillers can be liquid-cooled, air-cooled, or evaporatively cooled. Water or liquid-cooled chillers incorporate the use of cooling towers which improve the chillers' thermodynamic effectiveness as compared to air-cooled chillers. This is due to heat rejection at or near the air's wet-bulb temperature rather than the higher, sometimes much higher, dry-bulb temperature. Evaporatively cooled chillers offer higher efficiencies than air-cooled chillers but lower than liquid-cooled chillers.

Liquid-cooled chillers are typically intended for indoor installation and operation and are cooled by a separate condenser water loop and connected to outdoor cooling towers to expel heat to the atmosphere.

Air-cooled and evaporative cooled chillers are intended for outdoor installation and operation. Air-cooled machines are directly cooled by ambient air being mechanically circulated directly through the machine's condenser coil to expel heat to the atmosphere. Evaporative cooled machines are similar, except they implement a mist of water over the condenser coil to aid in condenser cooling, making the machine more efficient than a traditional air-cooled machine. No remote cooling tower is typically required with either of these types of packaged air-cooled or evaporatively cooled chillers.

Where available, cold water readily available in nearby water bodies might be used directly for cooling, replacing or supplementing cooling towers. The deep water source cooling system in Toronto, Ontario, Canada, is an example. It uses cold lake water to cool the chillers, which in turn are used to cool city buildings via a district cooling system. The return water is used to warm the city's drinking water supply, which is desirable in this cold climate. Whenever a chiller's heat rejection can be used for a productive purpose, in addition to the cooling function, very high thermal effectiveness is possible.

Vapor-compression chiller technology Current vapor-compression chiller technology is based on the "Reverse-Rankine cycle" known as vapor-compression. See the attached diagram which outlines the key components of the chiller system.

A vapor compression chiller typically uses one of four types of compressor: Reciprocating compression, scroll compression, screw-driven compression, and centrifugal compression are all mechanical machines that can be powered by electric motors, steam, or gas turbines. Using electric motors in a semi-hermetic or hermetic configuration is the most common method of driving the compressors since electric motors can be effectively and easily cooled by the refrigerant, without requiring fuel supply or exhaust ventilation and no shaft seals are required as the motor can operate in the refrigerant, reducing maintenance, leaks, operating costs and downtime, although open compressors are sometimes used. They produce their cooling effect via the reverse-Rankine cycle, also known as vapor-compression. With evaporative cooling heat rejection, their coefficients of performance (COPs) are very high; typically 4.0 or more.

COP

Key components of the chiller:

Refrigeration compressors are essentially a pump for refrigerant gas. The capacity of the compressor, and hence the chiller cooling capacity, is measured in kilowatts input (kW), Horse power input (HP), or volumetric flow (m3/h, ft3/h). The mechanism for compressing refrigerant gas differs between compressors, and each has its own application. Common refrigeration compressors include reciprocating, scroll, screw, or centrifugal. These can be powered by electric motors, steam turbines, or gas turbines. Compressors can have an integrated motor from a specific manufacturer, or be open drive--allowing the connection to another type of mechanical connection. Compressors can also be either hermetic (welded closed) or semi-hermetic (bolted together).

In recent years, application of variable-speed drive (VSD) technology has increased efficiencies of vapor compression chillers. The first VSD was applied to centrifugal compressor chillers in the late 1970s and has become the norm as the cost of energy has increased. Now, VSDs are being applied to rotary screw and scroll-technology compressors.

Condensers can be air-cooled, liquid-cooled, or evaporative. The condenser is a heat exchanger which allows heat to migrate from the refrigerant gas to either water or air. Air cooled condenser are manufactured from copper tubes (for the refrigerant flow) and aluminium fins (for the air flow). Each condenser has a different material cost and they vary in terms of efficiency. With evaporative cooling condensers, their coefficients-of-performance (COPs) are very high; typically 4.0 or more. Air cooled condensers are installed and operated outdoors and are cooled with outside air, that is often forced through the condenser using electric fans. Water or liquid cooled condensers are cooled with water that is often in turn cooled by a cooling tower.

The expansion device (TEV) or refrigerant metering device (RMD) restricts the flow of the liquid refrigerant causing a pressure drop that vaporizes some of the refrigerant; this vaporization absorbs heat from nearby liquid refrigerant. The RMD is located immediately prior to the evaporator so that the cold gas in the evaporator can absorb heat from the water in the evaporator. There is a sensor for the RMD on the evaporator outlet side which allows the RMD to regulate the refrigerant flow based on the chiller design requirement.

Evaporators can be plate type or shell and tube type. The evaporator is a heat exchanger which allows the heat energy to migrate from the water stream into the refrigerant gas. During the state change of the remaining liquid to gas, the refrigerant can absorb large amounts of heat without changing temperature.

How absorption technology works